Authorized distributor in Vietnam: Tan Vien Fire Protection Technology JSC 0982 419 033 [email protected] VIEN中文

Addressable wireless fire alarm – Series 200A

DAS-WDM-200AHandheld radio signal detection module

Radio survey module of the Tan Vien Series 200A addressable wireless fire alarm system.

  • Scans channels 0–17, detects occupied channels
  • Simulates end devices, measures RSSI / SNR at the installation position
  • Plugs into the CODER-F100E programmer via USB, no software needed
  • Used for surveys, acceptance and maintenance of the 200A system
Price on request

Support device for surveys, installation and maintenance. Plug it into the CODER-F100E handheld programmer via USB to scan channels (check whether a channel is occupied) and simulate end devices — measuring RSSI/SNR right at the planned installation position before construction.

0 – 17channels scanned RSSI · SNRquantitative measurement ≈ 11 gplug-and-play

Key features

  • Channel scan. Displays a signal-strength curve: ≈ −120 dBm is a clear channel; > −100 dBm continuously for > 1 min is a busy channel.
  • Device simulation. Simulates smoke/heat detectors, call points, sounder beacons and I/O to measure the radio signal at the installation position.
  • Displays Total / Success / RSSI / SNR. Assesses link quality before the position is finalized.
  • Plug-and-play. Plug the USB into the CODER-F100E, no software installation; with overcurrent and overvoltage protection.

Indicator status

Power On when plugged into the CODER-F100E
Comm On while simulating a device

Usage notes

  • Power only from the CODER-F100E programmer.
  • The device to be simulated must first be registered on the panel.
  • Measure ≈ 10 times at each position; pass when RSSI ≥ −100 dBm and SNR > 0.

For the detailed radio survey procedure, see section 4 of Series 200A Design, Installation and Operation Manual (PDF).

Applications

Position survey · Signal strength measurement · Channel check · Handover · Periodic maintenance

DAS-WDM-200A technical specifications

Model DAS-WDM-200A
Operating voltage 24 VDC (supplied by the CODER-F100E)
Operating current Channel scan < 3 mA · simulation < 20 mA (peak)
Frequency / transmit power 312 – 316 MHz / ≤ 20 dBm
Receiver sensitivity −126 dBm
Transmission range 200 m (unobstructed)
Compatible panel DAS-FACP-200A
Dimensions 53 × 45 × 13 mm
Weight ≈ 11 g
Housing / color ABS / black
Environment −20 °C to +60 °C; RH 5 – 95 %
Reference standards Installation accessory — use together with the CODER-F100E