Authorized distributor in Vietnam: Tan Vien Fire Protection Technology JSC 0982 419 033 [email protected] VIEN中文

Addressable wireless fire alarm – Series 200A

DAS-WCP-200AAddressable wireless emergency manual call point

Manual call point of the Tan Vien Series 200A addressable wireless fire alarm system.

  • Reusable plastic pressing plate, restored with a key
  • Fire alarm current < 1.5 mA, Li-MnO₂ 3 V battery
  • 3-colour LED indicating monitoring / fire alarm / fault
  • Mounted at 1.4 ± 0.2 m height on escape routes
Price on request

Manual fire alarm call point with an integrated LoRa module. When a fire is detected, the user presses the plate and the device immediately sends a fire signal to the panel. The plastic plate is reusable and is restored with a dedicated key.

1000 munobstructed transmission ≈ 3 yearsbattery life (Level I) 90×90×43mm

Key features

  • Reusable pressing plate. After pressing, restore it with the dedicated key — no parts to replace.
  • Ultra-low consumption. Monitoring current < 100 µA, fire alarm current < 1.5 mA.
  • 3-colour indicator. Green – Red – Yellow indicate monitoring, fire alarm, fault and low battery.
  • Moisture-proof coated circuit. Wax-dipped circuit board and a silicone cap on the button improve resistance to moisture and corrosion.

Indicator status

Power-on Green flashes once
Monitoring Green flashes once every ≈ 6 min
Fire alarm Red steady
Call point fault Yellow flashes once every ≈ 2 s
Low battery (< 2.75 V) Yellow flashes once every ≈ 30 s

Installation notes

  • Mount at 1.4 ± 0.2 m height, on escape routes and stair landings, clearly visible.
  • Spacing between call points ≤ 45 m; distance from the exit of any room to a call point ≤ 30 m.
  • Do not install where the temperature > +40 °C or humidity is excessive.

For detailed network registration, installation and commissioning procedures, see Series 200A Design, Installation and Operation Manual (PDF).

Suitable installation locations

Escape routes · Stair landings · Corridors · Lobbies · Building exits

DAS-WCP-200A technical specifications

Model DAS-WCP-200A
Rated voltage DC 3 V (1 Li-MnO₂ CR17505 battery)
Average monitoring current < 100 µA
Fire alarm current < 1.5 mA
Frequency / transmit power 312 – 316 MHz / ≤ 20 dBm
Receiver sensitivity −126 dBm
Transmission range 1000 m (unobstructed – manufacturer's figure)
Actuating element Reusable plastic pressing plate, restored with a key
Dimensions 90 × 90 × 43 mm
Weight ≈ 139 g
Housing / color ABS / red
Environment Indoor; −10 °C to +55 °C; RH ≤ 95 %
Reference standards TCVN 7568-11 (ISO 7240-11) · TCVN 7568-25:2023

The 1000 m range is a manufacturer's figure measured in an unobstructed space. For indoor design in reinforced-concrete buildings, use a radius of ≈ 25 m around the panel/repeater (≈ 15 m in factories with heavy interference), and a radio survey is mandatory: pass when RSSI ≥ −100 dBm, SNR > 0.

Related products

Get a quote

Tan Vien Fire Protection Technology JSC · Authorized distributor in Vietnam