Addressable wireless fire alarm – Series 200A
DAS-WSB-200AWireless combined fire alarm sounder beacon
Sounder beacon of the Tan Vien Series 200A addressable wireless fire alarm system.
- Sound pressure level 76–95 dB, flashing 1.5–2.0 Hz
- Modulated tone, 3–5 s cycle
- Activated and reset from the control panel
- Plug-in base, ceiling or wall mounting; reports a fault when removed
Combined sounder beacon with an integrated LoRa module. On receiving an activation command from the panel, the device emits a high-intensity red flashing light and a modulated alarm tone to warn of evacuation. Press “Reset” on the panel to return it to monitoring.
Key features
- Ultra-bright LEDs. Multiple high-brightness LEDs: easy to notice, long life, low consumption.
- High-power piezo speaker. High-efficiency drive circuit, loud sound, energy saving.
- Modulated tone. Tone-change cycle of 3 – 5 s — not mistaken for ambient sounds.
- Plug-in base – upper/lower covers. Fast installation, battery replacement and maintenance; reports a fault when removed from the base.
- Control from the panel. Activated by interlock or manually; reset from the panel.
Indicator status
| Power-on / seated in base | Green flashes once |
|---|---|
| Monitoring | Green flashes once every ≈ 6 min |
| Alarm | Red steady + flashing light + sounder |
| Low battery (< 2.75 V) | Yellow flashes once every ≈ 30 s |
Installation notes
- The sound level at every point must exceed the background noise by ≥ 10 dBA (≥ 15 dBA in sleeping areas).
- Do not obstruct the beacon and speaker; mount it correctly on its base — removing it from the base triggers a fault.
- Test operation at least once every quarter.
For detailed network registration, installation and commissioning procedures, see Series 200A Design, Installation and Operation Manual (PDF).
Suitable installation locations
DAS-WSB-200A technical specifications
| Model | DAS-WSB-200A |
|---|---|
| Rated voltage | DC 3 V (Li-MnO₂ CR17505 battery pack) |
| Average monitoring current | < 100 µA |
| Average alarm current | < 250 mA |
| Frequency / transmit power | 312 – 316 MHz / ≤ 20 dBm |
| Receiver sensitivity | −126 dBm |
| Transmission range | 1000 m (unobstructed – manufacturer's figure) |
| Sound pressure level | 76 – 95 dB |
| Flash frequency / tone-change cycle | 1.5 – 2.0 Hz / 3.0 – 5.0 s |
| Weight | ≈ 194 g |
| Mounting | Plug-in base, ceiling or wall mounting |
| Environment | Indoor; 0 °C to +55 °C; RH ≤ 95 % |
| Reference standards | TCVN 7568-3 (ISO 7240-3) · ISO 7240-23 · TCVN 7568-25:2023 |
The 1000 m range is a manufacturer's figure measured in an unobstructed space. For indoor design in reinforced-concrete buildings, use a radius of ≈ 25 m around the panel/repeater (≈ 15 m in factories with heavy interference), and a radio survey is mandatory: pass when RSSI ≥ −100 dBm, SNR > 0.
Related products
DAS
DAS-FACP-200A
Addressable wireless fire alarm control panel
Price on request
DAS
DAS-WSD-200A
Addressable wireless photoelectric smoke detector
Price on request
DAS
DAS-WHD-200A
Addressable wireless fixed-temperature heat detector
Price on request
DAS
DAS-WCP-200A
Addressable wireless emergency manual call point
Price on request
DAS
DAS-WIO-200A
Wireless I/O control module