Authorized distributor in Vietnam: Tan Vien Fire Protection Technology JSC 0982 419 033 [email protected] VIEN中文

Addressable wireless fire alarm – Series 200A

DAS-WSB-200AWireless combined fire alarm sounder beacon

Sounder beacon of the Tan Vien Series 200A addressable wireless fire alarm system.

  • Sound pressure level 76–95 dB, flashing 1.5–2.0 Hz
  • Modulated tone, 3–5 s cycle
  • Activated and reset from the control panel
  • Plug-in base, ceiling or wall mounting; reports a fault when removed
Price on request

Combined sounder beacon with an integrated LoRa module. On receiving an activation command from the panel, the device emits a high-intensity red flashing light and a modulated alarm tone to warn of evacuation. Press “Reset” on the panel to return it to monitoring.

≤ 95 dBsound pressure level 1.5–2 Hzflash frequency 1000 munobstructed transmission

Key features

  • Ultra-bright LEDs. Multiple high-brightness LEDs: easy to notice, long life, low consumption.
  • High-power piezo speaker. High-efficiency drive circuit, loud sound, energy saving.
  • Modulated tone. Tone-change cycle of 3 – 5 s — not mistaken for ambient sounds.
  • Plug-in base – upper/lower covers. Fast installation, battery replacement and maintenance; reports a fault when removed from the base.
  • Control from the panel. Activated by interlock or manually; reset from the panel.

Indicator status

Power-on / seated in base Green flashes once
Monitoring Green flashes once every ≈ 6 min
Alarm Red steady + flashing light + sounder
Low battery (< 2.75 V) Yellow flashes once every ≈ 30 s

Installation notes

  • The sound level at every point must exceed the background noise by ≥ 10 dBA (≥ 15 dBA in sleeping areas).
  • Do not obstruct the beacon and speaker; mount it correctly on its base — removing it from the base triggers a fault.
  • Test operation at least once every quarter.

For detailed network registration, installation and commissioning procedures, see Series 200A Design, Installation and Operation Manual (PDF).

Suitable installation locations

Corridors · Lobbies, public areas · Escape stairwells · Basements · Factories

DAS-WSB-200A technical specifications

Model DAS-WSB-200A
Rated voltage DC 3 V (Li-MnO₂ CR17505 battery pack)
Average monitoring current < 100 µA
Average alarm current < 250 mA
Frequency / transmit power 312 – 316 MHz / ≤ 20 dBm
Receiver sensitivity −126 dBm
Transmission range 1000 m (unobstructed – manufacturer's figure)
Sound pressure level 76 – 95 dB
Flash frequency / tone-change cycle 1.5 – 2.0 Hz / 3.0 – 5.0 s
Weight ≈ 194 g
Mounting Plug-in base, ceiling or wall mounting
Environment Indoor; 0 °C to +55 °C; RH ≤ 95 %
Reference standards TCVN 7568-3 (ISO 7240-3) · ISO 7240-23 · TCVN 7568-25:2023

The 1000 m range is a manufacturer's figure measured in an unobstructed space. For indoor design in reinforced-concrete buildings, use a radius of ≈ 25 m around the panel/repeater (≈ 15 m in factories with heavy interference), and a radio survey is mandatory: pass when RSSI ≥ −100 dBm, SNR > 0.

Related products

Get a quote

Tan Vien Fire Protection Technology JSC · Authorized distributor in Vietnam