Authorized distributor in Vietnam: Tan Vien Fire Protection Technology JSC 0982 419 033 [email protected] VIEN中文

Addressable wireless fire alarm – Series 200A

DAS-WHD-200AAddressable wireless fixed-temperature heat detector

Heat detector of the Tan Vien Series 200A addressable wireless fire alarm system.

  • Class B heat detector, operating up to +65 °C
  • Suitable for kitchens, garages, machine rooms, storerooms
  • Li-MnO₂ 3 V battery, ≈ 3 years (Level I), low-battery self-report
  • LoRa transmission 312–316 MHz, 1000 m unobstructed
Price on request

Heat detector with an integrated LoRa module that continuously measures ambient temperature; when the threshold is exceeded it activates the local light and sounder and sends a fire signal to the panel. For places where fires generate a lot of heat, or where smoke detectors are prone to false alarms.

1000 munobstructed transmission ≈ 3 yearsbattery life (Level I) +65 °Cmaximum operating temperature

Key features

  • Epoxy-coated heat sensor. Good electrical insulation and stability; unaffected by dust, steam or kitchen smoke.
  • Suited to heat-generating areas. Kitchens, garages, machine rooms, storerooms — where smoke detectors are prone to false alarms.
  • Sounder + 3-colour LED. Local warning, clearly indicating monitoring / fire / fault / low battery.
  • One-button registration / deletion. Fast installation, no software needed.

Indicator status

Power-on Green flashes once
Monitoring Green flashes once every ≈ 6 min
Fire alarm Red steady + sounder ≈ 4 s per cycle
Sensor / button fault Yellow flashes once every ≈ 2 s + short beep
Low battery (< 2.75 V) Yellow flashes once every ≈ 30 s + short beep

Installation notes

  • Use where fires generate a lot of heat; do not use where fires mainly produce smoke.
  • Do not install where the ambient temperature > +65 °C or humidity is excessive.
  • Layout per Table 2 of TCVN 5738:2021 (ceiling ≤ 3.5 m: ≤ 25 m², spacing ≤ 5 m).

For detailed network registration, installation and commissioning procedures, see Series 200A Design, Installation and Operation Manual (PDF).

Suitable installation locations

Kitchens · Garages, basements · Machine rooms, technical rooms · Storerooms · Heat-generating areas

DAS-WHD-200A technical specifications

Model DAS-WHD-200A
Rated voltage DC 3 V (1 Li-MnO₂ CR17505 battery)
Average monitoring current < 100 µA
Average fire alarm current < 20 mA (with sounder)
Frequency / transmit power 312 – 316 MHz / ≤ 20 dBm
Receiver sensitivity −126 dBm
Transmission range 1000 m (unobstructed – manufacturer's figure)
Battery life ≈ 3 years (Level I) · up to ≈ 5 years (Level II)
Dimensions Ø 115 × 48 mm
Weight ≈ 134 g
Housing / color ABS / white
Environment Indoor; −10 °C to +65 °C; RH ≤ 95 %
Reference standards TCVN 7568-5 (ISO 7240-5) · TCVN 7568-25:2023

The 1000 m range is a manufacturer's figure measured in an unobstructed space. For indoor design in reinforced-concrete buildings, use a radius of ≈ 25 m around the panel/repeater (≈ 15 m in factories with heavy interference), and a radio survey is mandatory: pass when RSSI ≥ −100 dBm, SNR > 0.