DAS wired addressable fire alarm · Sanjiang devices used in DAS systems
J-SAP-M-A62E-ExIntrinsically safe (explosion-proof) addressable manual call point
Addressable manual call point, intrinsically safe type Ex ib IIC T6 Gb, for hazardous areas with a fire and explosion risk.
- Certified to GB 19880 & GB/T 3836.1 & GB/T 3836.4
- Type of explosion protection
- Fully electronic coding; the address can be reset on site with an address programmer
Price on request
Addressable manual call point, intrinsically safe type Ex ib IIC T6 Gb, for hazardous areas with a fire and explosion risk.
Key features
- Certified to GB 19880 & GB/T 3836.1 & GB/T 3836.4
- Type of explosion protection: intrinsically safe
- Fully electronic coding; the address can be reset on site with an address programmer
- Can directly control external devices
- Resettable push button
J-SAP-M-A62E-Ex technical specifications
| Model | J-SAP-M-A62E-Ex |
|---|---|
| Operating voltage | 24V loop |
| Operating current | Quiescent current: <300 µA; alarm current: <1 mA |
| Explosion-protection marking | Ex ib IIC T6 Gb |
| Dimensions (with base) | 90×90×43 mm (W×H×D) |
| Operating environment | Operating temperature: -10 °C to 55 °C; relative humidity: ≤ 95% (non-condensing at 40 °C ±2 °C) |
| Standards | GB 19880 & GB/T 3836.1 & GB/T 3836.4 |
| Brand | Sanjiang |