DAS wired addressable fire alarm · Sanjiang devices used in DAS systems
C9060TConventional manual call point (EN54-11)
Conventional Sanjiang manual call point complying with EN54-11, with PCCC fire protection equipment inspection certificate.
- Non-polarized contacts
- 3-layer conformal-coated circuit board, 304 stainless-steel contacts
- Robust construction
Original manufacturer documents: Datasheet (EN) · EN54 catalogue 2025 (EN) · EN54 catalogue – Vietnamese translation
Conventional manual call point C9060T (EN54)
Conventional manual call point C9060T (EN54-11)
The manual call point C9060T is a manual fire alarm device that has passed the PCCC equipment inspection and meets the standard EN54-11, ensuring quality and reliability in the fire alarm system. It is an ideal choice for buildings that require a fast and accurate fire warning system.
Key features
- Non-polarized contacts, which simplifies installation, wiring and maintenance of the system.
- 3-layer conformal-coated electronic circuit board against moisture and corrosion, combined with 304 stainless-steel contacts, so the device operates reliably even in environments with acid or alkali vapors or high humidity.
- Robust design, ensuring durability and long-term operation.
- High-grade ABS plastic housing, good heat resistance and impact resistance.
- Operating voltage: DC 18–28V, suitable for many fire alarm systems.
- Protection rating: IP30, ensuring stable operation in indoor environments.
- Operating temperature: from -10°C to 55°C, humidity ≤ 95% (non-condensing).
- Low current consumption, saving energy.
This device can be mounted on a wall or back box, suitable for many types of buildings such as offices, factories, hotels and shopping centers.
C9060T technical specifications
| Model | C9060T |
|---|---|
| Type | Conventional manual call point |
| Applicable standard | EN 54-11:2001 + A1:2005 |
| Certification | LPCB (BRE Global Ltd, United Kingdom) No. 1426d-(cl-2); reference code 1426d/02 |
| Operating voltage | DC 24 V (20–28 V) |
| Monitoring current | 0 mA |
| Alarm current | < 30 mA |
| Operating environment | Indoor installation; −10 °C to +55 °C; humidity ≤ 95 % (non-condensing at 40 °C ± 2 °C) |
| Dimensions (W × H × D) | 90 × 90 × 42 mm |
| Weight | Approx. 105 g (including base) |
| Actuating element | Plastic push plate, reset with a special tool, reusable |
| Indicator | Off in normal state, steady on in alarm |