Fire alarm system · Fire alarm system (EN54)

A9054TAddressable 4-channel input/output module (EN54)

4-channel addressable input/output module for Sanjiang EN54 fire alarm control panels: 4 supervised inputs, 4 relay outputs, with built-in short-circuit isolator.

  • Standards EN 54-17, EN 54-18
  • 4 dry-contact outputs, 2 A / 30 VDC
  • Occupies 4 consecutive addresses on the loop
Price on request

Original manufacturer documents: User manual (EN) · User manual – Vietnamese translation · EN54 Catalogue 2025 (EN) · EN54 Catalogue – Vietnamese translation

The A9054T addressable input/output module is used with Sanjiang addressable fire alarm control panels (EN54 series). Each module provides 4 independent inputs and 4 independent relay outputs, and occupies 4 consecutive addresses on the loop.

Applications

  • Control of fire-protection interlocked devices: smoke extraction dampers, pressurization air supply dampers, fire dampers…
  • Receives feedback signals from these devices to determine their operating status.
  • Each input can be configured at the control panel as a status input or an alarm input.

Features

  • Complies with EN 54-17 (short-circuit isolators) and EN 54-18 (input/output devices).
  • Built-in short-circuit isolator on the loop.
  • Electronic coding; addresses are written on site with a coding tool.
  • Two-wire loop connection, snap-in mounting, transparent cover for easy viewing of the indicators.

A9054T technical specifications

Model A9054T
Type 4-channel addressable input/output module: 4 supervised inputs, 4 relay outputs
Standards EN 54-17, EN 54-18
Operating voltage DC 20–28 V
Operating current Standby < 3 mA; alarm < 6 mA; short-circuit < 15 mA
Output contacts 4 dry-contact outputs, 2 A @ 30 VDC
Input modes Mode 1: normally open; mode 2: normally closed; mode 3: fire alarm and device fault reporting. Open-circuit and short-circuit supervision by end-of-line resistor
Addressing Electronic coding on site using a coding tool; address range 1–321; each module occupies 4 consecutive addresses
Short-circuit isolation Built-in. Isolation voltage 7–14 V; recovery voltage 1.4–17 V; rated current 1 A, maximum operating current 3 A; leakage current when isolated ≤ 8.5 mA; normal internal resistance ≤ 0.1 Ω
Indicator LEDs Green: flashes every 12 s during polling, steady on when the output relay is activated. Red: flashes rapidly on input fault, steady on when the input is activated. Yellow: on when the bus is short-circuited
Installation Snap-in mounting with multiple installation options; transparent cover allows the indicators to be seen
Wire cross-section 0.2–2.5 mm²
Environment Indoor use, −10 °C to +55 °C; humidity ≤ 95 % (40 °C ± 2 °C, non-condensing)
Dimensions 103 × 136 × 23 mm
Weight Approx. 139 g