Authorized distributor in Vietnam: Tan Vien Fire Protection Technology JSC 0982 419 033 [email protected] VIEN中文

Standalone wireless fire alarm – Series 200

DAS-WHD-200Standalone wireless heat fire detector

Heat detector of the Tan Vien Series 200 standalone wireless fire alarm system.

  • Temperature-based fire detection — for kitchens, garages, machine rooms
  • Alarm current < 20 mA, local sounder
  • Lithium-manganese 3 V battery, ≈ 5 years
  • Inspected under 82/KĐ-PCCC, type-conformity certified to QCVN 47:2015/BTTTT

Part of the Series 200 standalone wireless fire alarm line. Does your project need a control panel that shows the location of each detector? See the Series 200A addressable wireless fire alarm system.

Price on request

Heat detector with an integrated wireless module that continuously measures ambient temperature and raises an alarm when the threshold is exceeded. For places where fires generate a lot of heat, or where smoke / steam is frequently present and smoke detectors are prone to false alarms.

≈ 5 yearsbattery life 200 munobstructed range < 20 mAalarm current

Key features

  • Real-time heat sensor. Continuously collects temperature readings and alarms when the preset threshold is exceeded.
  • Local sounder. Three beeps repeated about every 4 s on fire alarm.
  • Self-monitoring. Reports sensor faults and low battery < 2.75 V.
  • Replaces smoke detectors where steam is heavy. Kitchens, garages, generator rooms… wherever smoke detectors are unsuitable.

Indicator status

Power-on / seated in base Green flashes once
Normal monitoring Green flashes once every ≈ 6 min
Fire alarm Red steady + 3 beeps / ≈ 4 s
Sensor fault Yellow flashes once every ≈ 2 s + beep
Low battery (< 2.75 V) Yellow flashes once every ≈ 30 s + beep

Installation notes

  • For places where fires generate a lot of heat, or where smoke and steam are frequently present.
  • Do not install where the ambient temperature > +40 °C or air velocity > 15 m/s.
  • Layout per TCVN 5738:2021 (ceiling ≤ 3.5 m: ≤ 25 m² per detector, spacing ≤ 5 m).

For detailed pairing, installation and commissioning procedures, see Series 200 Installation, Operation and Maintenance Manual (PDF). Operating principle: Series 200 diagrams and simulation.

Legal documents: Inspection certificate 82/KĐ-PCCC (PDF) · Type-conformity certificate QCVN 47:2015/BTTTT (PDF).

Suitable installation locations

Kitchens · Garages, basements · Generator rooms · Laundry and drying rooms · Storerooms with steam

DAS-WHD-200 technical specifications

Model DAS-WHD-200
Rated voltage DC 3 V – lithium-manganese battery
Monitoring / alarm current < 100 µA / < 20 mA
Frequency / transmit power 444.4 – 444.8 MHz / ≤ 17 dBm
Receiver sensitivity −126 dBm
Communication range ≤ 200 m (unobstructed)
Battery life ≈ 5 years (normal conditions)
Dimensions / weight Ø 115 × 48 mm / ≈ 134 g
Housing White ABS plastic
Environment Indoor; −10 °C to +50 °C; RH ≤ 95 %
Legal / standards Inspection certificate 82/KĐ-PCCC · QCVN 47:2015/BTTTT type conformity · reference TCVN 7568-5

The communication range is a manufacturer's figure measured in an unobstructed space. Indoors, the signal attenuates through walls and concrete floors — always test the alarm at the actual installation position and add a DAS-WMS-200 as a repeater when needed.

Related products

Get a quote

Tan Vien Fire Protection Technology JSC · Authorized distributor in Vietnam