Standalone wireless fire alarm – Series 200
DAS-WCP-200Standalone wireless manual call point
Manual call point of the Tan Vien Series 200 standalone wireless fire alarm system.
- Reusable plastic pressing plate, restored with a key
- Alarm current < 1.5 mA, battery ≈ 5 years
- Wall-mounted at 1.4 m height on escape routes
- Inspected under 82/KĐ-PCCC, type-conformity certified to QCVN 47:2015/BTTTT
Part of the Series 200 standalone wireless fire alarm line. Does your project need a control panel that shows the location of each detector? See the Series 200A addressable wireless fire alarm system.
Manual fire alarm call point with an integrated wireless module. When a fire is detected, the user presses the plate to activate all sounder beacons in the system. The plastic plate is reusable and is restored with a dedicated key.
Key features
- Reusable pressing plate. No glass to break; restore with the dedicated reset key.
- 3-colour indicator. Red: fire alarm · Yellow: fault / low battery · Green: normal.
- Ultra-low consumption. Alarm current < 1.5 mA, lithium-manganese battery ≈ 5 years.
- Red ABS housing, moisture-proof coated circuit. Durable and easy to recognize on escape routes.
Indicator status
| Power-on / seated in base | Green flashes once |
|---|---|
| Normal monitoring | Green flashes once every ≈ 6 min |
| Fire alarm | Red steady |
| Call point fault | Yellow flashes once every ≈ 2 s |
| Low battery (< 2.75 V) | Yellow flashes once every ≈ 30 s |
Installation notes
- Mount on the wall at 1.4 ± 0.2 m height, on escape routes and stair landings, clearly visible.
- Spacing between call points ≤ 45 m; distance from the exit of any room to a call point ≤ 30 m.
- Keep the reset key in the security room — an activated call point must be restored with the key.
For detailed pairing, installation and commissioning procedures, see Series 200 Installation, Operation and Maintenance Manual (PDF). Operating principle: Series 200 diagrams and simulation.
Legal documents: Inspection certificate 82/KĐ-PCCC (PDF) · Type-conformity certificate QCVN 47:2015/BTTTT (PDF).
Suitable installation locations
DAS-WCP-200 technical specifications
| Model | DAS-WCP-200 |
|---|---|
| Rated voltage | DC 3 V – lithium-manganese battery |
| Monitoring / alarm current | < 100 µA / < 1.5 mA |
| Frequency / transmit power | 444.4 – 444.8 MHz / ≤ 20 dBm |
| Receiver sensitivity | −126 dBm |
| Communication range | ≤ 200 m (unobstructed) |
| Battery life | ≈ 5 years (normal conditions) |
| Dimensions / weight | 90 × 90 × 43 mm / ≈ 139 g |
| Housing | Red ABS plastic; plastic pressing plate restored with a key |
| Environment | Indoor; −10 °C to +55 °C; RH ≤ 95 % |
| Legal / standards | Inspection certificate 82/KĐ-PCCC · QCVN 47:2015/BTTTT type conformity · reference TCVN 7568-11 |
The communication range is a manufacturer's figure measured in an unobstructed space. Indoors, the signal attenuates through walls and concrete floors — always test the alarm at the actual installation position and add a DAS-WMS-200 as a repeater when needed.
Related products
DAS
DAS-WSD-200
Standalone wireless photoelectric smoke fire detector
Price on request
DAS
DAS-WMS-200
Wireless fire alarm control hub with integrated sounder beacon
Price on request
DAS
DAS-WHD-200
Standalone wireless heat fire detector
Price on request
DAS
DAS-WIO-200
Wireless I/O module
Price on request
DAS
DAS-653L
Wireless remote reset
Price on request