DAS wired addressable fire alarm · Control panels
DAS-FACP-A100/A200Addressable 1-loop fire alarm control panel
DAS-series 1-loop addressable fire alarm panel for small and medium projects: mini apartment buildings, boarding houses, mixed residential-commercial buildings, kindergartens.
- A100: 100 devices; A200: 200 devices per loop
- 2.8-inch color LCD
- Loop cable up to 2,000 m, with surge protection
Original manufacturer documents: DAS wired fire alarm catalogue (Tan Vien, 10/2026)
Operating principle and connection diagram of the DAS addressable fire alarm control panel
The DAS-FACP-A100/A200 addressable fire alarm control panel is a dedicated intelligent addressable fire alarm solution, designed and manufactured to meet demanding project requirements such as durable, stable operation in special environments (high humidity, corrosion resistance) and fast, intuitive fire detection. The DAS-FACP-A100/A200 has a single loop with 100/200 devices per loop. The DAS-FACP-A100/A200 is suitable for small and medium-sized projects: mini apartment buildings, boarding houses, mixed residential-commercial buildings, kindergartens, etc.
Technical specifications
- 2.8-inch color LCD display.
- Number of loops: 1 loop
- Devices per loop: A100 – 100 devices; A200 – 200 devices (detectors and modules alike)
- Maximum loop cable length: 2000 m
- Built-in surge protection on the mains power line.
- Built-in surge protection circuit for each loop of the fire alarm panel.
- Built-in Ethernet communication interface (RJ45) for networking up to 254 fire alarm panels, with no limit on transmission distance.
- Built-in CAN communication interface: up to 60 panels can be connected in the same system.
- The panel can place phone calls and send SMS fire alerts to designated phone numbers.
- The panel supports 5-status SMS messages: fire alarm, fault, malfunction, etc.
- The panel allows loop wiring in a branch (T-tap) topology combined with short-circuit isolator modules, keeping the system stable and isolating the fire-damaged or faulty section from the system so that the other zones continue to operate normally.
- The panel has a built-in printer for logging faults and events.
- The panel uses non-polarized device technology, which makes installation, operation and maintenance easier.
- The panel has a large control-script library that makes system programming convenient and simple and covers most control requirements, similar to a PLC (Programmable Logic Controller).
- The panel integrates a 220 VAC – 24 VDC conversion circuit using pulse-width modulation technology, which improves DC power quality and extends the service life of the fire alarm equipment. The power circuit includes an intelligent battery charging module to extend the life of the panel's batteries.
DAS-FACP-A100/A200 technical specifications
| Model | DAS-FACP-A100/A200 |
|---|---|
| Type | Single-loop addressable fire alarm control panel |
| Capacity | A100: 100 devices; A200: 200 devices (detectors or modules) |
| Max. loop length | 2,000 m |
| Display | 2.8-inch color LCD |
| Connectivity | Ethernet RJ45 (networks up to 254 panels); CAN (60 panels) |
| Phone calls and SMS | Fire alarm calls and SMS to designated numbers; 5-status SMS (fire, fault, malfunction, etc.) |
| Protection | Surge protection on the mains power line and on each loop |
| Printer | Built-in event printer |
| Main power supply | 187–242 VAC / 50 Hz |
| Standby power supply | 24 VDC (2 × 12 VDC / 2.8 Ah batteries) |
| Output current | 1 A @ 24 VDC |
| Environment | 0 °C to +55 °C; humidity ≤ 95 % |
DAS