Fire alarm system · Fire alarm system (EN54)
SEC3004Fire alarm control panel
Key features
- EN54-2&EN54-4 certified by LPCB and Applus.
- 7.0 inch color touch-sensitive screen LCD, resolution of 800×480.
- 324 addresses for 1 loop,max 4 loops.
- A maximum of 5000 fire protection zones are supported.More user-friendly Night Mode Time Range Settings.
- Networkable: CAN bus for interconnection of up to 60 FACPs and Ethernet for up to 254 FACPs.
- Fire alarm, fault, C&E and operation, each category can store up to 10000 records
Price on request
The SEC3004 control panels are touch-sensitive, addressable fire detection panels, with up to 4 circuits for the SEC3004, each panel supporting up to 324 addressable points, and are designed to meet the requirements of the EN 54-2 & EN 54-4 standards for simple installation, easy operation and easy maintenance.
Technical Parameters:
| Power supply | ||
| Mains supply | 110V/230V AC(-15%,+10%),50Hz/60Hz | |
| Mains fuse | T4A250V | |
| Operating voltage | 28V±0.5VDC | |
| Recommended mains cable | Standard/black mains cable, cable size 1mm² | |
| Power rating | Imax.a=3.1A; Imax.b=5.55A; Imin=0.3A | |
| Max. battery supply current | 8A(when the Mains is disconnected) | |
| Max. charging current | 1A | |
| Physical dimensions | 440×400×180mm(2×12V/12Ah Battery) | |
| Max. internal resistance of battery | 1Ω | |
| Approx.weight(without battery) | 9Kg | |
| Battery fuse | 15A | |
| Quiescent current (full loaded) | <0.3A | |
| Outputs | ||
| S.C.Out (+, -) | Output voltage | 20~28V DC |
| Max. output current | 1A | |
| End of line resistor | 10KΩ | |
| Cable diameter | 1mm² ~ 2.5mm² | |
| F.A. Out (+, -) | Output voltage | 20~28V DC |
| Max. output current | 50mA | |
| End of line resistor | 10KΩ | |
| Cable diameter | 1mm² ~ 2.5mm² | |
| Fault Out(NC, COM, NO) | Contact capacity | 2A@24V DC |
| Cable diameter | 1mm² ~ 2.5mm² | |
| AUX 24V (+, -) | Output voltage | 20~28V DC |
| Max. output current | 2A | |
| Cable diameter | 1mm² ~ 2.5mm² | |