Fire alarm system · Fire alarm system (EN54)
SEC1000Fire alarm control panel
Key features
- Up to 120 addresses on one loop.
- The loop supports class A and Class B types.
- An easy to read, 4.3"color screen LCD with a resolution of 480×272.
- Zone indicators for 16 zones gives a quick indication of the location of an alarm.
- Record capacity of 1000 historical events for each of historical fire, historical fault and historical operation.
- An independently programmable conventional sounder circuit output.
- Integral power supply and battery.
- Flexible and intuitive cause and effect programming on front panel.
- Zone test, point test and module start/stop testing facilitate the commissioning.
- U-disk interface makes the load and save of configuration or historical data convenient for system commissioning and maintenance.
- Hierarchy management with three access levels.
- Anti-tamper protection by a key lock.
- CAN bus for interconnection of up to 20 FACPs.
Price on request
The purpose of the SEC1000 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance.
The SEC1000 panel is an addressable fire detection panel with 1 loop of 120 addressable points and expansion capabilities. It is compatible with other peripherals made by Sanjiang with its own protocol.
Technical Parameters:
| Mains supply | 110V/230VAC (-15%, +10%). 50Hz/60Hz. |
| Mains fuse | T3.15AL250V |
| Operating voltage | 20 ~ 28VDC |
| Recommended mains cable | Standard/black mains cable, cable size 0.75mm2 |
| Power rating | Imin=0.45A; Imax.a=1.15A; Imax.b=1.65A |
| Max. battery supply current | 3A (when the Mains is disconnected) |
| Max. charging current | 1A |
| Battery capacity, type and recommended model | NP7-12 for 7Ah VRLA(Yuasa) |
| Max. internal resistance of battery | 1Ω |
| Battery fuse | F6AL250V |
| Quiescent current (full loaded) | < 0.4A |
| S.C.Out (+, -) | Output voltage: 20 ~ 28VDC Max. output current: 800mA, 1A S.C.Out+24VK in total End of line resistor: 47K ohm 0.25W Recommended type of cable: Plain unscreened cable, 1.5mm2 Cable diameter:1mm2 ~ 2.5mm2 Transmission distance:≤1500m |
| F.A. Out (+, -) | Output voltage: 20 ~ 28VDC Max. output current: 100mA End of line resistor: 47K ohm 0.25W Recommended type of cable: Plain unscreened cable, 1.5mm2 Cable diameter: 1mm2 ~ 2.5mm2 Transmission distance: ≤1500m |
| FAULT OUT(COM, NO) | Contact capacity: 30VDC@2A, [email protected] |
| 24VK (+, -) | Recommended type of cable: Plain unscreened cable, 1.5mm2 Cable diameter: 1mm2 ~ 2.5mm2 Output voltage: 20 ~ 28VDC Max. output current: 500mA, 1A S.C.Out+24VK in total Recommended type of cable: Plain unscreened cable, 1.5mm2 Cable diameter: 1mm2 ~ 2.5mm2 |
| LOOP OUT (+, -) LOOP IN (+, -) | Output voltage:18.5 ~ 28VDC, pulse Max. output current: 500mA Loop type: Class A and Class B Recommended type of cable: Unscreened twisted-pair, 1.5mm2 Max. Loop length: 2000m(Class A) Cable diameter: 1mm2 ~ 2.5mm2 |
| RS-485 | Transmission rate: 9600 bps Recommended type of cable: Unscreened twisted-pair, 1mm2 Transmission distance: ≤1000m Cable diameter: 1mm2 ~2.5mm2 |
| CAN | Max. number of panels: 20 Transmission rate: Optional: 10K, 20K, 50K and 100K bps Recommended type of cable: Unscreened twisted-pair, 1mm2 Transmission distance: ≤1000m Cable diameter: 1mm2 ~ 2.5mm2 |
| Approx. Dimensions of the panel (W×H×D) | 400×360×104mm |
| Approx. weight (without battery) | 3.7kg |
| Operating conditions | Temperature range: -5°C~ 45°C; Max relative humidity: 95% (40°C ± 2°C, no condensation) |