Fire alarm system · Fire alarm system – CCC (previous models)
JK-A52Econventional detector monitoring module
Addressable module that connects conventional smoke detectors, heat detectors and call points to an addressable fire alarm panel.
- Up to 25 conventional detectors, unlimited call points
- Compatible with conventional detectors of many brands
- GB 16806 certified
Original manufacturer documents: Specifications & instructions (EN) · Sanjiang CCC catalogue (EN) · CCC system installation guide (EN) · CCC catalogue – Vietnamese translation (part 1) · CCC catalogue – Vietnamese translation (part 2)
- Zone module for conventional detectors: receives fire signals from conventional photoelectric smoke detectors, conventional heat detectors and conventional manual call points.
- The module can be integrated with conventional fire detection devices of the following brands: GST/China; Horing/China; Chungmei/Taiwan; Woosung/Korea; Firesmart/Vietnam; Unipos, Hochiki; Siemens; etc.
- GB 16806 certified.
- The address is set with a handheld programmer, which is very quick and convenient.
- The module has non-polarized contacts, so installation, wiring, operation and maintenance are very convenient.
- Up to 25 conventional detectors (photoelectric smoke and heat detectors combined), with no limit on the number of manual call points.
- 12-month warranty
Technical specifications
Addressable module for conventional fire alarm devices: conventional photoelectric smoke detectors, conventional heat detectors, conventional call points
Non-polarized module.
Weight: 110g
Dimensions: 86x86x35mm
Standby current: <0.5mA, operating current <2mA.
Open-circuit detection end-of-line resistor: 4.7 kΩ.
Housing made of high-grade ABS plastic.
12-month warranty
JK-A52E technical specifications
| Model | JK-A52E |
|---|---|
| Type | Conventional detector monitoring module (4-wire connection) |
| Standard | GB 16806-2006 |
| Operating voltage | DC 24 V |
| Standby current | < 0.5 mA (bus); < 15 mA (power line) |
| Activated current | < 2 mA (bus); < 35 mA (power line) |
| Addressing | Set on site with the programmer, address 1–324 |
| Indicator | Test LED flashes every 12 seconds; steady on when activated |
| Environment | −10 °C to +50 °C; humidity ≤ 95 % (40 °C ± 2 °C, non-condensing) |
| Dimensions | 86 × 86 × 35 mm (with base) |
| Weight | Approx. 110 g (with base) |
Related products
JB-QBL-A104E
Fire alarm control panel
Price on request
JB-QBL-A108E
Fire alarm control panel
Price on request
JB-QBL-A220E
Fire alarm control panel
Price on request
JTY-GD-A30E
Point-type Photoelectric Smoke Detector
Price on request
JB-QBL-DK520E
fire equipment power supply monitoring panel
Price on request