Fire alarm system · Fire alarm system – CCC (previous models)
GL-A59Eshort-circuit isolator module
Module that isolates a shorted or damaged loop section so that the rest of the system keeps operating, and restores automatically when the fault is cleared.
- Fewer than 32 devices per isolated branch
- Non-polarized, 3-layer conformal-coated circuit
- Dimensions 86 × 86 × 35 mm
Price on request
Original manufacturer documents: Specifications & instructions (EN) · Sanjiang CCC catalogue (EN) · CCC system installation guide (EN) · CCC catalogue – Vietnamese translation (part 1) · CCC catalogue – Vietnamese translation (part 2)
- The short-circuit isolator module isolates short circuits and recovers automatically once the fault is removed. It can isolate a fire alarm section that has a problem (fire, damage, short circuit, etc.) so that the system keeps operating normally in the other sections without affecting the loop.
- Stable communication technology with strong noise immunity.
- Fast activation response of the powered loop.
- Plug-and-play design, making installation and maintenance easy and convenient.
- 12-month warranty
Technical specifications
- The module is non-polarized, which makes wiring of devices during construction, installation, operation, maintenance and servicing very convenient.
- The module's electronic circuit board has a 3-layer conformal coating against moisture and corrosion, so it works well in humid and coastal areas.
- The number of devices on one branch of the short-circuit isolator module is fewer than 32.
- Dimensions: 86*86*35mm (W*H*D) (with base)
- Operating environment: -10°C ~ +55°C; RH ≤ 95% (40°C ± 2°C, non-condensing)
GL-A59E technical specifications
| Model | GL-A59E |
|---|---|
| Type | Loop short-circuit isolator module |
| Wiring | Two-wire, non-polarized; base DZ-A59 |
| Operating current | Standby < 0.5 mA; activated < 9 mA |
| Maximum branch resistance | 10 Ω |
| Isolation conditions (per manufacturer's documentation) | Current > 2 A; voltage < 16 V DC |
| Indicator | Yellow: normally off, lit when isolating |
| Environment | −10 °C to +55 °C; humidity ≤ 95 % (40 °C ± 2 °C, non-condensing) |
| Dimensions | 86 × 86 × 35 mm (with base) |
| Weight | Approx. 125 g (with base) |
Related products
JB-QBL-A104E
Fire alarm control panel
Price on request
JB-QBL-A108E
Fire alarm control panel
Price on request
JB-QBL-A220E
Fire alarm control panel
Price on request
JTY-GD-A30E
Point-type Photoelectric Smoke Detector
Price on request
JB-QBL-DK520E
fire equipment power supply monitoring panel
Price on request