Fire alarm system · Fire alarm system (EN54)
A9020TAddressable Heat Fire Detector
Key features
- LPCB and CPR approval
- It supports soft addressing and rewriting the address via coder in situ.
- Within a single-chip microcomputer, it can collect real-time data and then process it to realize a curve tracing for the field situation.
A9020T point-type heat fire detector (Detector hereunder) is a mated product of the SEC3002 fire alarm control panel. It uses a two-bus work mode. With an internal microprocessor, it supports electronic coding. The detector realizes real-time acquisition of the in situ temperature data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel. When in a routing inspection, the detector indicator will blink. When there is a fire in the monitored area and the temperature has reached the alarm threshold, the fire alarm control panel will confirm a fire alarm according to the received message sent from the detector, and the detector indicator will light at the same time to indicate a fire alarm.
The detector is suitable for such industrial and civil buildings that have a great deal of heat when fire takes place, such as kitchens, boiler rooms, generator rooms, drying workshops and smoking rooms and is not suitable for places with a great deal of smoke but little heat.
Technical Parameters:
| Executive standard | EN54-5 |
| Operating voltage | 24V (pulse modulation) |
| Standby current | <0.3mA |
| Alarm current | no remote indicator <1.5mA , has remote indicator <3.5mA |
| Work indication | The red indicator will blink in the monitoring status or remain lit in the alarm status |
| Weight | around 115g(with the base) |
| Product Category | A2 |
| Dimension | diameter: 100mm, height: 60mm (with the base) |
| Wiring | non-polarity two-bus system (L1, L2); the terminal 2 and 4 can connect with the remote indicatorOperating environmentIndoors |
| Temperature | -10℃~+50℃ |
| Relative humidity | ≤95% (no condensation) |
| Coding | It can realize electron ic coding via coder in situ. Address codes 1 to 324 are available for selection. |
| Matched host machine | SEC3002 fire alarm control panel |