DAS wired addressable fire alarm · Addressable modules
DAS-OMAddressable output module
Addressable output module of the DAS series, for use with DAS-FACP panels.
- Powered 24 VDC output, < 50 mA to drive an interposing relay
- 2-wire non-polarized bus, electronic coding
- Controls pumps, fans, valves, rolling shutters and emergency broadcast
Price on request
The output module DAS-OM is an addressable module that controls peripheral devices in the DAS addressable fire alarm system. Its powered 24 VDC output (current < 50 mA) drives an interposing relay, which in turn controls the components of the fire protection system according to the interlock program of the control panel.

Applications
- Control of fire pumps and solenoid valves of the fire suppression system.
- Control of pressurization fans and smoke exhaust fans.
- Control of fire dampers, throttle valves, rolling shutters and fire curtains.
- Switching of emergency broadcast and background music.
Features
- 2-wire non-polarized signal bus, simple wiring, powered from the loop.
- Fully electronic coding; the address can be reset on site with a handheld programmer.
- Input/output status indicator on the module face.
- Plug-in design on a base for easy installation and maintenance.
DAS-OM technical specifications
| Model | DAS-OM |
|---|---|
| Type | Addressable output module (output control) |
| Compatible systems | DAS-FACP-A324 / DAS-FACP-A100/A200 addressable fire alarm control panels |
| Operating voltage | 24 VDC loop (2-wire bus, non-polarized) |
| Operating current | Normal < 1 mA; activated < 20 mA |
| Output capability | 24 VDC, current < 50 mA (drives an interposing relay) |
| Address coding | Electronic coding, set with a handheld programmer |
| Dimensions | 86 × 86 × 40 mm (including base) |
| Operating environment | -10 °C ÷ +55 °C; relative humidity ≤ 95 % (non-condensing) |
| Installation | Surface-mounted on a wall or in the BOX-M6S module box |